ELECTRICAL POWER SYSTEM STUDIES
Understand how your electrical network performs and where improvements are needed. ESUK provides electrical power system studies to support safer operation, reliable supplies and informed investment decisions. We can scope an individual study or combine services around your site’s requirements.
Our engineering team works alongside our electrical safety management and training specialists. We also support incident investigations and work with enforcing authorities where required. Speak to us about your network, planned changes or operational concerns.
Fault currents can exceed the capability of electrical equipment, creating risks to people, plant and continuity of supply.
A short-circuit study calculates prospective fault levels and compares them with relevant equipment ratings. It helps identify where equipment or protection needs further review, including when your network changes.
The Electricity at Work Regulations 1989 include duties relating to system construction, equipment capability and protection against excess current.
Regulation 4 addresses electrical systems and work activities that could pose a danger.
Regulation 5 addresses the strength and capability of electrical equipment.
Regulation 11 addresses protection against excess current.
A current short-circuit study can support decisions about equipment suitability and provide evidence for electrical safety management. It does not, on its own, demonstrate compliance with every applicable duty.
How the study helps
Short-circuit analysis can help you:
Support compliance with relevant electrical safety duties.
Improve the safety and reliability of your power system.
Inform the review of protective devices and settings.
Prioritise remedial actions.
Identify areas where fault levels may exceed equipment ratings.
Circuit breakers, fuses and relays help protect electrical systems against faults and overloads. Coordinating them aims to disconnect the affected section promptly while limiting disruption elsewhere.
A protection coordination study reviews device selection and settings to balance fault clearance, equipment protection and continuity of supply. It can also inform arc flash risk reduction, as clearing time affects incident energy.
We analyse device characteristics and time-current curves to identify grading issues and recommend suitable settings. Recommendations consider equipment capabilities and operating requirements, rather than simply removing all overlap between curves.
Effective protection supports the duties under the Electricity at Work Regulations 1989 relating to safe systems and excess current.
Regulation 4 addresses the safe construction and maintenance of systems.
Protection must be considered across the network because a device in one location may protect equipment elsewhere.
Regulation 11 addresses the provision of protection against excess current where needed to prevent danger.
The study provides evidence to support your electrical safety arrangements and highlights actions needed to improve protection.
How the study helps
Identify coordination issues, review the suitability of protection and reduce avoidable disruption from unnecessary trips. Findings can also highlight equipment ratings that need checking, along with a fault-level study.
ESUK helps you balance selective isolation and equipment protection against the operating needs of your power system. Discuss your protection coordination requirements with our engineering team.
The Dangerous Substances and Explosive Atmospheres Regulations 2002 (DSEAR) require employers to assess and control relevant workplace safety risks from dangerous substances. These include fire, explosion and, where applicable, substances corrosive to metals.
Examples include flammable liquids and vapours, gases and combustible dusts such as flour or wood dust. The assessment must consider the substances present and how they are used, stored or generated.
Key employer duties include:
How ESUK can help
We can review your arrangements against applicable DSEAR requirements, identify gaps and help you plan remedial actions. Contact us to discuss a DSEAR gap analysis.
An effective earthing system is essential to electrical safety. ESUK assesses existing installations to identify deficiencies and recommend improvements. Where suitable, non-invasive techniques can reduce the need for plant outages.
Depending on the installation and scope, the assessment may include:
How the study helps
Identify potentially dangerous touch and step voltages and assess whether earthing supports the intended operation of protective devices. Findings help you prioritise improvements and support electrical safety management.
Starting large motors can cause voltage dips that affect equipment across your site.
These dips may interrupt other loads, slow motors, or affect process performance. A motor starting study assesses the proposed starting method, supply characteristics and connected loads to identify whether the effects are acceptable. The need for a study depends on the installation, not on a single percentage threshold.
The scope can range from a voltage drop assessment to dynamic modelling of motor acceleration, torque, current and bus voltage. We tailor the analysis to your operating requirements.
How the study helps
Check initial performance, identify unacceptable voltage dips and compare options to reduce their impact. The findings support decisions about starting methods, supply capacity and reliable operation.
Stability analysis examines how your electrical system responds to disturbances such as faults, switching, load changes, motor starting or the loss of generation.
Depending on the system, the study may assess fault clearing times, generator behaviour, motor acceleration and recovery, load shedding, bus transfer timing and relay settings. We agree on the scenarios and scope around your network.
How the study helps
Identify vulnerabilities and evaluate measures to improve recovery from disturbances, supporting the reliability and availability of your electrical supply.
Load flow analysis models how power moves through your electrical network under defined operating conditions.
It provides information about voltages, loading and losses, helping you assess capacity and make better use of existing infrastructure.
The study can support network design, planned expansion and the review of operating arrangements. It helps compare options for capital investment and running costs.
How the study helps
Variable speed drives and other electronic equipment can introduce harmonics into electrical systems. Harmonic distortion may contribute to overheating, interference and equipment problems.
We use measurements and modelling, as appropriate, to assess voltage and current distortion. Where mitigation is needed, analysis can help evaluate filter options before implementation.
The study considers how filters interact with power factor correction equipment and how the system behaves under different load conditions.
Harmonic analysis can help investigate:
How the study helps
Determine whether harmonic performance meets your connection requirements and identify appropriate mitigation measures. Any financial implications depend on your supply agreement.
Harmonic distortion can contribute to:
Reliability analysis estimates the performance of your electrical distribution system using equipment data, network configuration and defined assumptions. It helps compare improvement options and identify where failures may have the greatest operational impact.
Depending on the scope, the report may include:
We can use failure mode and effects analysis to inform maintenance priorities and intervals. Recommendations reflect your operating needs and can include preventive maintenance and non-invasive condition monitoring to reduce avoidable shutdowns.
We also advise on spare parts planning and supplier arrangements, helping you balance resilience with the capital held in stock.
How the study helps
Inform maintenance and investment priorities.
Identify opportunities to improve reliability and availability.
Review spare parts holdings against operational risk.
Power factor describes the relationship between real power and apparent power. A low power factor may increase demand charges or other supply costs, depending on your tariff and connection arrangements.
ESUK reviews your supply tariff and a suitable period of your electricity bills, typically 6 to 24 months, to understand your existing usage and charges.
We assess whether power factor correction could provide benefits, including lower charges, released capacity and reduced system losses. Recommendations should also consider the interaction with harmonics.
How the study helps
Assess potential savings against your actual tariff.
Identify opportunities to improve capacity and efficiency.
Over voltages can arise from lightning, switching and other events in electrical networks.
Insulation coordination considers equipment withstand levels, the over voltages it may experience, and the protection provided.
A study assesses relevant overvoltage scenarios and helps determine suitable insulation levels and protective measures. It supports decisions about equipment specification and reduces the risk of damage.
How the study helps
Inform equipment and protection specifications.
Reduce vulnerability to overvoltage damage and associated disruption.
ESUK carries out lightning risk assessments using applicable IEC standards to establish protection requirements for structures and electrical systems. Experience includes refineries, substations, data centres, water treatment works, manufacturing facilities and pharmaceutical sites.
For existing installations, the assessment may include a site survey. For new projects, design drawings and specifications can inform the study, with further information requested where needed.
We also provide independent reviews of existing and proposed lightning protection designs, helping clients assess recommendations from designers and installers.
A review can support decisions about upgrades, insurance requirements or concerns over a design’s alignment with applicable standards.
How the study helps
Understand lightning protection requirements and prioritise improvements.
Support decisions that improve resilience and reduce the risk of damage. Contact ESUK to discuss your electrical power system study requirements.
ARC FLASH FAQs
An arc flash is a sudden release of electrical energy caused by a fault or short circuit. It can produce intense heat, bright light, pressure, molten metal, and hazardous sound levels—creating serious risks to anyone nearby.
Arc flash incidents can cause severe burns, blindness, hearing damage, electrical shock, respiratory injuries, and other life-threatening harm. The resulting pressure wave may also throw workers or cause flying debris and equipment damage.
Arc flashes may result from:
Incorrect operation of electrical equipment
Yes. Although the potential energy and incident severity vary by system, arc flash hazards can exist in low-voltage electrical equipment as well as medium- and high-voltage systems.
Potentially hazardous equipment may include:
Other energised electrical equipment
A qualified electrical professional should evaluate the electrical system and determine where arc flash hazards may exist. An arc flash risk assessment may include system data collection, short-circuit analysis, protective-device coordination, incident-energy calculations, equipment labelling, and recommendations for reducing risk.
An arc flash risk assessment is a structured evaluation used to identify electrical hazards, estimate potential incident energy, establish approach boundaries, determine appropriate protective measures, and support safe work practices.
The need for an assessment depends on the equipment, system configuration, available fault current, operating conditions, and applicable workplace requirements. A qualified person should determine the appropriate scope for each facility.
Incident energy is the amount of thermal energy that may reach a worker during an arc flash, typically expressed in calories per square centimetre. It can help determine the level of arc-rated clothing and other protective equipment required.
Arc-rated clothing is designed and tested to reduce the severity of burn injuries during an arc flash. The required clothing and personal protective equipment depend on the hazard and the results of the risk assessment.
Not necessarily. Flame-resistant clothing is intended to resist ignition and continued burning, while arc-rated clothing is tested specifically for exposure to an electric arc. Protective clothing should be selected based on the identified electrical hazard and applicable requirements.
An arc flash label may provide information such as:
Labels should be read carefully and kept current when system conditions or equipment change.
No. Personal protective equipment does not eliminate the hazard or prevent an arc flash from occurring. It is a last line of defence used together with de-energisation, engineering controls, safe work practices, training, and appropriate equipment maintenance.
Whenever feasible, electrically safe work conditions should be established before work begins. If equipment must remain energised, the work should be justified, planned, and performed only by qualified workers using appropriate procedures, boundaries, tools, and protective equipment.
Only properly trained and qualified workers should perform tasks that may expose them to electrical hazards. Employers should ensure workers understand the equipment, hazards, work procedures, limitations, and required protective measures.
An assessment should be reviewed whenever significant changes are made to the electrical system, including changes to transformers, generators, utility service, protective devices, equipment, or operating configurations. It should also be reviewed when an incident or unexpected operating condition indicates that existing information may no longer be accurate.
Risk-reduction measures may include:
Do not operate or work on equipment that appears damaged, overheated, contaminated, or otherwise unsafe. Keep others away from the area and report the condition to a supervisor or qualified electrical professional immediately.
Yes. Our team can help evaluate electrical systems, perform arc flash studies, provide equipment labelling, recommend risk-reduction measures, and support safe electrical work practices. Contact us to discuss your facility and project requirements.
Safety disclaimer: Arc flash hazards should be evaluated by qualified electrical professionals. This information is provided for general educational purposes and does not replace a site-specific risk assessment, training, safe work procedures, or applicable laws and standards.